K560 - Carte 16 Canaux Entrée/Sortie pour Centrale de Détection Incendie Kentec 16 Channel Input/Output BoardK560 - Carte 16 Canaux Entrée/Sortie pour Centrale de Détection Incendie Kentec 16 Channel Input/Output Board
Print

16 Channel Input/Output Board SYNCRO IO

16 Channel Input/Output Board for Kentec Fire Detection Panel SYNCRO IO K560
Description

K560 - 16 Channel Input/Output Board for Kentec Fire Detection Panel SYNCRO IO

To add more I/O capability to the extensive options already offered by the Syncro Fire Detection panel, up to thirty two, sixteen channel I/O boards may be connected.
The 16 channel boards may be mixed on the RS485 bus with 8 way sounder boards, 6 way sounder boards or 4 way conventional Fire detection zone boards to provide a very flexible system of I/O to satisfy any requirement.
When using a simple two wire RS485 communications protocol, these boards may be mounted locally to the Fire Detection panel or distributed on a bus up to 1200 metres long by using a suitable cable.
The flexibility of these boards is further enhanced by the fact that each of the channels is configurable as either an input or and output.
Each channel may also be configured to produce a variety of input actions or respond to a variety of output types.
All channels can contribute to, or respond to, system wide cause and effects logic.
Typical uses for I/O boards include geographical LED mimic displays and plant alarm inputs.
Standard Syncro Fire Detection panels contain fixings for one sounder, relay, conventional Fire detection or I/O board, which can easily be connected using four small signal wires to the power and comms bus within the Fire Detection panel.
Consideration must be taken as to the loading on the main panel.

FEATURES & BENEFITS

- 16 channels
- Each channel configurable as input or output
- Inputs opto-isolated
- Outputs open collector transistor
- Simple 2 wire connection to Fire Detection panel
- Up to 32 boards supported per panel (512 Input/Output Channels)
- Inputs and outputs configurable as per field devices
- Full cause and effects on all inputs and outputs
- Multi drop RS485 communications
- Can be used with other Syncro I/O modules on the same panel
- Compatible with Syncro AS Fire Detection panels

TECHNICAL SPECIFICATIONS

  • Product code : K560
  • Supply voltage : 21 - 30VDC
  • Quiescent current : 20mA
  • Current per input : 3mA (maximum)
  • Current per output : 100mA (maximum)
  • Communications : RS485 two wire
  • Maximum distance from panel : 1.2Km (using correct type of cable)
  • PCB size : 190mm x 61mm
  • Cable capacity : 2.5mm per terminal
  • Operating temperature : -10°C to +50°C
  • Operating humidity : To 95% (non condensing)


A question ?

Worldwide Shipping

Short About Us

Ornicom leans on more than 40 years of experience to propose a large and innovative range of safety integrated system.

By bringing a personalized answer to their specific problems, we accompany our customers, stage after stage, towards the success of their projects.

Find Out More

Our customers

Need a Catalog ?

Our Services

Ordering

Delivery options

Payment methods

After-sales Services

 

 

Help

Search a Product

Contact Us

Sitemap

Conditions of Special Offers

 

 

 

Ornicom Security products

© 1989 - 2024 Ornicom All Rights Reserved.
 
6830 Bouillon, Belgium
Tel:+32 477 23 76 79
Fax:+32 61 48 01 51
E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.
 
Payment methods
JUMP TO TOP