Nitrogen Dioxide Gas Detector, NO2 Gas Detector 0-20 ppm 4-20mA - Intrinsically Electrochemical cell - SMART3G-C2 Sensitron Explosion Proof Enclosure version Zone 1 category 2 areas S3008ND

My Wishlist
Compare

S3008ND - NITROGEN DIOXIDE Gas Detector (NO2) 0-20 ppm, 4-20mA - Intrinsically Electrochemical cell - Explosion Proof Enclosure Version SMART3G-C2 Zone 1 category 2 areas

S3008ND SMART3G gas detectors are employed to detect Nitrogen Dioxide, NO2 Gas compounds (ppm) in classified areas.
Gas detector with intrinsically safe protection ATEX II 2G Ex db [ib] IIC T6 Gb

For the toxic gas detection, Sensitron has operated a reliable selection among the most performing electrochemical cells to supply units representing the state of the art in toxic gas detection.

Designed to meet with industrial requirements, the SMART3G-C2 allow to monitor toxic, flammable and refrigerant gas contents in industrial environments and classified areas.
Ideal in industrial environments, the SMART3G-C2 feature one man calibration via the STS/CKD+ calibration keypad.
The SMART3G-C2 can reliably monitor flammable compounds (% LFL), toxic compounds and refrigerant gases in ppm, Oxygen and CO2 contents in % by Vol.
They do also monitor refrigerant gases both in ppm and % LFL.
The detectors are rated to IP65.

IEC60079-29-1 - SIL2 - Atex Ex - IEC - IECEx

FEATURES & BENEFITS

  • Standard 4-20 mA 3 wire output
  • Optional 1 or 3 relay output
  • Optional RS485 interface for Modbus communication.
  • Zero tracking to maintain the zero point steady from possible drifts
  • Ongoing system self diagnosis
  • ATEX II 2G Ex db IIC T5 Gb (standard marking) (II2 GD with optional adapter)
  • ATEX II 2G Ex db [ib] IIC T6 Gb for detectors with intrinsically safe protection
  • SIL 2 HW & SIL3 SW certified
  • Wide range of sensors and detectable gases
  • Wide range of accessories for installation and maintenance
  • Easy sensor replacement

Important note:

On request, SMART3G-C2 can be supplied:
- with 25m remote sensor kit to separate the sensor head from the transmitter

 

Gas Detector type : Nitrogen Dioxide Gas Detector, NO2 Gas Detector

Recently Viewed

Our Services

Ordering

Delivery options

Payment methods

After-sales Services

Help

Search a Product

Contact Us

Sitemap

Conditions of Special Offers

Ornicom Security products

© 1989 - 2025 Ornicom All Rights Reserved.
 
6830 Bouillon, Belgium
Tel:+32 477 23 76 79
Fax:+32 61 48 01 51
E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.