Digital LHD Cable 185°C (365°F) w/ Nylon coating PROLINE TH185

273,00 €
Total without tax: 273,00 €
SKU: TH185
Blank_165x165

Digital Linear Heat Detection (LHD) cable 155°C (365°F) with Nylon coating PROLINE - TH185

Length - Longueur
My Wishlist
Compare

TH185 - Digital LHD Cable 185°C (365°F) w/ Nylon coating ProLine

The TH185 is a Digital Linear Heat Detection (LHD) cable with a 185°C (365°F) fixed temperature activation rating. The High Temperature coated linear heat cable is manufactured from two different types of nylon, with the outer sheath being a chemical resistant material. Commonly used in high temperature areas, hazardous and safe areas where chemicals such as hydrocarbon fuel oils, diesel, kerosene etc. are present. It is supplied in 100m, 200m, 500m and 1000m lengths.
Proline Digital Linear Heat Detection Cable uses fixed temperature detection technology to provide an easy method for sensing changes in temperature levels. The cable can offer alternative overheat protection in a vast range of applications and environments, from tunnels, cable trays, warehousing to sensing changes in temperature within escalators and other applications where many risks of fire are hidden from view.
The digital linear heat detection cable can be directly connected to a single zone of a conventional fire alarm control panel, or, using an addressable zone/switch monitor, the digital linear heat detection cable can easily be interfaced to an addressable loop.
Digital linear heat detection cable is comprised of a pair of twisted low resistance, tri-metallic conductors, sheathed in advanced temperature sensitive polymers. When the cable reaches the required temperature the two twisted cores will fuse together, with a fire triggering resistor attached to the input interface and a single core of linear heat cable to activate an alarm at the main fire panel.

FEATURES & BENEFITS

  • UL 521 approved File No S36573
  • Detection at any point along the cable
  • Low installation and maintenance costs
  • Reliable solution for hazardous areas
  • 185°C (365°F) Activation temperature

  Other Reference : ProReact F1069, AD185N

   

Recently Viewed

Our Services

Ordering

Delivery options

Payment methods

After-sales Services

Help

Search a Product

Contact Us

Sitemap

Conditions of Special Offers

Ornicom Security products

© 1989 - 2025 Ornicom All Rights Reserved.
 
6830 Bouillon, Belgium
Tel:+32 477 23 76 79
Fax:+32 61 48 01 51
E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.