Extinguishant Fire Detection Panel DS-40 SIGMA XT
K11031M2 - Extinguishant Fire Detection Panel DS-40 SIGMA XT Kentec
Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma XT extinguishant releasing fire detection panel offers outstanding value and performance for all small to medium fixed fire fighting installations.
With three fire detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.
The extensive configuration options of the Sigma XT allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-1).
The fire detection panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety.
The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.
With all of the electronics mounted on a single, easily removable, steel plate Sigma XT fire detection panels are both robust and easy to install.
Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range.
FEATURES & BENEFITS
- Complies with EN12094-1
- Three detection zones as standard
- Any single zone or any combinations of zones can be configured to release
- Configurable first stage sounder delays
- Configurable detection delays
- Zero time delay upon manual release option
- Compatible with I.S. barriers
- Non-latching zone input option to receive signals from other systems such as aspirating equipment
- Configurable extinguishant delays up to 60 seconds in 5 second steps
- Configurable extinguishant duration up to 5 minutes in 5 second steps
- Countdown timer shows time remaining until release
- Supports up to seven, four wire status indicators
- Built in Extract Fan control
Programmable Functions
Access Level 2
- Test Zones 1 to 3
- Disable Zones 1 to 3
- Disable 1st Stage Alarms
- Disable Pre-activated 1st Stage Relay
- Disable Pre-activated 2nd Stage Relay
- Disable Extract Fan Output
- Disable Manual Release Input
- Disable Extinguishant Sub System
- Activate Extract Fan Output
- Activate Alarm Delays
Access Level 3
- Sounder Delay
- Coincidence Detection
- Disable Panel Features
- Zone Alarm Delays (Detectors)
- Zone Alarm Delay (Call Points)
- Configure Zone for I.S Barrier Use
- Zone Short Circuit Alarm
- Zone Non Latching
- Zone Inputs Delay
- Extinguishant Release Time Delay
- Extinguishant Release Duration Timer
- Extinguishant Reset Delay Timer
TECHNICAL SPECIFICATIONS
- Construction : 1.2 mm mild sheet steel
- Finish : Epoxy powder coated
- Colour - lid & box : BS 00 A 05 grey - fine texture
- Colour - control plate & labels : RAL 7047 light grey - satin
- Supply voltage : 230 VAC +10%/-15% (100 Watts maximum)
- Mains supply fuse : 1.6 Amp (F1.6A L250V)
- Power supply rating : 3 Amps total including battery charge 28V +/- 2V
- Maximum ripple current : 200 millivolts
- Battery type (Yuasa NP) : Two 12 Volt 7Ah sealed lead acid in series
- Battery charge voltage : 27.6 VDC nominal (temperature compensated)
- Battery charge current : 0.7 A maximum
- Battery fuse : 20mm, 3.15 A glass
- Maximum current draw from batteries : 3 Amps
- Quiescent current of panel in mains fail : 0.095 A
- ROV output : Fused at 500 mA with electronic fuse
- Sounder outputs : 24V Fused at 500 mA with electronic fuse
- Fault relay contact rating : 30 VDC 1A maximum
- Local relay fire contact rating : 30 VDC 1A maximum
- Fire relay contact rating : 30 VDC 1A maximum
- First stage contact rating : 30 VDC 1A maximum
- Second stage contact rating : 30 VDC 1A maximum
- Extract contact rating : 30 VDC 1A maximum
- Zone quiescent current : 2 mA maximum
- Terminal capacity : 0.5 mm© to 2.5 mm© solid or stranded wire
- Number of detector per zone : Dependent on type (maximum 32)
- Number of sounder per zone : Dependent on type (max. 0.5A per sounder circuit)
- Detection circuit end of line : 6K8 5% 1/2 Watt resistor
- Monitored input end of line : 6K8 5% 1/2 Watt resistor
- Sounder circuit end of line : 10K 5% 1/4 Watt resistor
- Extinguishant output EOL : 1N4004 Diode
- No of detection circuits : 3
- No of sounder circuits : 2 x 1st Stage, 1 x 2nd Stage
- Extinguishant release output : Fused at 1 Amp
- Extinguishant release delay : Adjustable 0 to 60 seconds (in 5 second steps)
- Extinguishant release duration : Adjustable 60 to 300 seconds (in 5 second steps)
- SIL, AL, FLT, RST inputs : Switched -ve, max resistance 100 Ohms
- Zone normal threshold : 8K ohms to 1K ohms
- Detector alarm threshold : 999 ohms to 400 ohms
- Call point alarm threshold : 399 ohms to 100 ohms
- Short circuit threshold : 99 ohms to 0 ohm
- Head removal condition : 15.5 to 17.5 volts
- Cabling : FP200 or equivalent
- Monitored inputs normal threshold : 8k ohms to 1k ohms
- Monitored inputs alarm threshold : 999 ohms to 100 ohms
- Monitored inputs short circuit threshold : 99 ohms to 0 ohms
- Status unit/Ancillary board connection : Two wire RS485 connection
- Status unit power output : Fused at 500 mA with electronic fuse
- Dimension : 385 mm x 310 mm x 90 mm